Battery bank sizing can be one of the more complex and important calculations in your system design. If the battery bank is oversized, you risk not being able to keep it fully charged; if the battery bank is sized too small, you won't be able to run your intended loads for as long as you'd planned.
written by Chris Brown
Many renewable energy (RE) systems incorporate batteries. Batteries can be used in all types of systems including:
Photovoltaic or solar panels
Wind Power Systems using Wind Turbines
Hydroelectric generators
Hybrid Renewable Energy Ststems
Other DCpower sources
The energy stored in the batteries can then be used directly to power DC loads or it can be inverted to power AC loads. The batteries recommended for RE systems are deep cycle batteries. To ensure you have enough reserve capacity to provide the electricity you need (without running additional generators), invest the time to size your battery bank properly. Because of the various conditions affecting battery bank sizing, this process may be one of the more challenging calculations you’ll have to do when planning your RE system.
Before tackling the calculations, start by identifying a few key pieces of information:
Watt Hours of electricity usage per day
Number of Days of Autonomy
Depth of Discharge limit
Ambient temperature at battery bank
Electrical Usage
The first thing you’ll need to know is the amount of energy you’ll be consuming per day. It’s worth the time to do a careful evaluation of exactly what loads (appliances, electronics, etc.) you plan to use and for what lengths of time. Keep track of this information on a loads list; you’ll refer to this list often for sizing other components as well. Your final tally should be expressed in Watt-hours (Wh) per day. If you know the kilowatt hours (kWh) per day just multiply that number by 1,000 to determine the Watt-hours per day. (Example: 1.2 kWh = 1,200 Wh)
Days of Autonomy
Next, you must determine the number of days of battery back-up that you want to have on hand. In other words, if you are unable to charge your batteries by any means, and you still need to draw power, you must provide this additional storage by increasing the size of your battery bank. For solar panel
If you conclude that you need more then five days of battery backup, you may want to explore multiple sources of electricity generation or backup generator options (like a fossil-fueled generator). If your primary electricity source is wind power, determine the number of days when there is little or no wind. This information can be found in the data you’ve collected using your data-logging anenometer. Hydroelectric turbine systems are unique because they usually operate continuously, and therefore do not require extensive storage. If you’re sizing a battery bank to be used in conjunction with an on-demand fuel-powered generator, the number of days of backup will represent the number of days you wish to go without using your generator.
Depth of Discharge
Another factor to consider is the planned Depth of Discharge (DoD) of your battery bank. Flooed lead acid batteries (FLA), sealed AGM batteries and sealed gel batteries are all rated in terms of charge cycles. A single cycle takes a battery from its fully charged state, through discharge (use), then back to full charge via recharging. The depth of discharge is the limit of energy withdrawal to which you will subject the battery (or battery bank). DoD is expressed as a percent of total capacity. The further you discharge a battery, the fewer cycles that battery will be capable of completing. Simply stated, deeper discharge shortens battery life.
Battery Life based on Depth of Discharge
It’s recommended that you never discharge a deep-cycle battery below 50% of its capacity; however, many battery manufacturers recommend even shallower DoDs. For off-grid applications, a 25% DoD will extend battery life significantly. On the other hand, if you’re only using the batteries occasionally, as a backup system, you can factor in a DoD of 50% or perhaps more.
Temperature
Battery life and capacity are affected by temperature. Unlike PV modules
System Voltage
By this point, you will have identified your system voltage. This is typically 12V, 24V, or 48V.
Calculations
Once you’ve pinpointed all these variables, it’s time to calculate the size of your battery bank! Let’s go through the steps below, using the following example system:
A system load of 6,000 Watt-hours per day
Three Days of Autonomy (back up) needed
Planned Depth of Discharge (DoD): 40%
Battery bank ambient average low temperature 60° F.
A 48V system
Step
Process
Example
1
Identify total daily use in Watt-hours (Wh)
6,000 Wh/day
2
Identify Days of Autonomy (backup days); multiply Wh/day by this factor.
3 Days of Autonomy:
6,000 x 3 = 18,000 Wh
3
Identify Depth of Discharge (DoD) and convert to a decimal value. Divide result of Step 2 by this value.
40% DoD:
18,000 / 0.4 = 45,000 Wh
4
Derate battery bank for ambient temperature effect. Select the multiplier corresponding to the lowest average temperature your batteries will be exposed to. Multiply result from Step 3 by this factor. Result is minimum Wh capacity of battery bank:
Temp. in [degrees] F. Factor
80+ 1.00
70 1.04
60 1.11
50 1.19
40 1.30
30 1.40
20 1.59
60° F. = 1.11
45,000 x 1.11 = 49,950 Wh
5
Divide result from Step 4 by system voltage. Result is the minimum Amp-hour (Ah) capacity of your battery bank.
49,950 / 48 = 1,040 Ah
Selecting batteries to meet the Amp-hour capacity
Now that you know the Amp-hour (Ah) capacity that will give you the storage you need, you may need a little guidance in selecting specific batteries. Keep in mind that it’s best to keep the number of parallel strings of batteries to three or fewer. If you parallel more than three strings of batteries, you risk shortening battery life due to uneven charging1
When batteries are cabled together in series, the voltage is additive. For example, you can put two 12V, 100 Ah batteries in series for a 24V bank. The capacity of that bank would still be 100 Ah. When batteries are connected in parallel, the voltage remains constant and the Ah capacity is additive. In our example with the 12V, 100 Ah batteries, connecting them in parallel would result in a 12V system with a capacity of 200 Ah.
The batteries you select must meet both your system voltage requirements AND the Ah capacity you calculated. In our example of the 48V system, we calculated that we needed 1,040 Ah to produce 6,000 Wh per day with 3 days of storage. More than one configuration of batteries can meet this need. For example, you could have four 12V batteries in series, each with a capacity of 1,040 Ah or more. Or you could use eight 12V batteries wired in two parallel strings where each battery had a 520 Ah capacity. Or you could use twelve 2V batteries in series, again with appropriate Ah capacities. In any given case, there may be multiple solutions. Your choices will be limited by battery availability and budget.
Building the bank: Amps, then Volts
To build your bank, try first to select a battery that is rated close to the Ah capacity you calculated in Step 5 above. Ignore voltage for a moment. If you can’t find one that’s very close, look for one that has a capacity either one-half or one-third your needed Ah figure. These fractions represent the number of series strings of such batteries you would need, in parallel, to complete your bank (1/2 = 2 strings, 1/3 = 3 strings). Once you find a candidate battery, divide your system voltage by the battery’s voltage. This will give you the number of such batteries you would need in each series string.
The total number of individual batteries you will need to complete your battery bank will be the product of the number of strings needed to meet your Ah requirement and the number of batteries per string needed to meet your system voltage requirement.
Total # batteries in bank = (# series strings) X (# batteries per string)
You can then compare your candidate battery banks against price, size and availability. You may want to talk with people who have used these batteries and learn what their experiences have been, compare warranties and advertised features, and finally buy the batteries you feel are best for you.
In any battery-based RE system, batteries are a major component investment—second in cost only to the PV modules in most cases—and they are a critical part of the system. Careful planning and battery selection is vital to ensure that your battery bank meets your needs and provides many hundreds or thousands of charge cycles. Take your time, run the numbers more than once, and you’ll avoid the worst pitfalls of RE system design.
Renovus Energy : Battery Bank Sizing for Off-Grid Systems
These calculations are intended for off-grid systems, not for
grid-connected systems with battery backup.
PV system size
Ave. daily PV generation (kWh)1
Recommended battery capacity (kWh)2
Battery bank voltage6
Recommended battery capacity (Ah)2
Estimated cost of batteries7
Min.
Max.
Ave.
Min.3
Max.4
Ave.5
Min.3
Max.4
Ave.5
Min.
Max.
Ave.
1 kW
1.54
4.06
2.87
3.08
8.12
5.74
48
64
169
120
Due to recent market volatility in the cost of lead, it is next to
impossible to give a good cost estimate for a lead-acid battery bank at this
time.
As of mid-August, 2007, costs were around $400 per kWh of battery
capacity.
24
128
338
239
12
257
677
478
2 kW
3.08
8.12
5.74
6.16
16.2
11.5
48
128
338
239
24
257
677
478
12
513
1,353
957
3 kW
4.62
12.2
8.61
9.24
24.4
17.2
48
193
508
359
24
385
1,015
718
12
770
2,030
1,435
4 kW
6.16
16.2
11.5
12.3
32.5
23.0
48
257
677
478
24
513
1,353
957
12
1,027
2,707
1,913
5 kW
7.70
20.3
14.4
15.4
40.6
28.7
48
321
846
598
24
642
1,692
1,196
12
1,283
3,383
2,392
6 kW
9.24
24.4
17.2
18.5
48.7
34.4
48
385
1,015
718
24
770
2,030
1,435
12
1,540
4,060
2,870
7 kW
10.8
28.4
20.1
21.6
56.8
40.2
48
449
1,184
837
24
898
2,368
1,674
12
1,797
4,737
3,348
8 kW
12.3
32.5
23.0
24.6
65.0
45.9
48
513
1,353
957
24
1,027
2,707
1,913
12
2,053
5,413
3,827
9 kW
13.9
36.5
25.8
27.7
73.1
51.7
48
578
1,523
1,076
24
1,155
3,045
2,153
12
2,310
6,090
4,305
10 kW
15.4
40.6
28.7
30.8
81.2
57.4
48
642
1,692
1,196
24
1,283
3,383
2,392
12
2,567
6,767
4,783
1 Ave. daily PV generation (kWh) assumes a minimum
insolation for Binghamton NY of 2.2 hr/day of "full sun" (1000W/m2)
in December, a maximum of 5.8 hr/day in June, and an average of
4.1 hr/day annually, a year-to-year uncertainty of +/-11% (NREL data), and an
overall PV system efficiency factor of 0.70.
2 Recommended battery capacity (kWh or Ah) is set equal to
twice the average daily PV generation. For longest life, sealed
maintenance-free batteries (aka VRLA, gelled electrolyte, AGM, etc.) should
not be discharged to greater than 50% of their total capacity rating (at the
24hr discharge rate). As a rule-of-thumb, recommended battery capacity (in
kWh) turns out to be approximately 3x the PV system rating (in kW).
3Min. recommended battery capacity (kWh or Ah) is the
largest battery bank size that the PV system can recharge from 50%
depth-of-discharge (DoD) on an average mid-winter day.
Min. recommended battery capacity (kWh or Ah) assumes no other means of
battery charging other than the PV system. A battery bank of this size or
smaller would be fully charged (on average) by the PV system every day
of the year without other charging sources. This is usually the best
choice unless expected daily energy usage is more than 1/2 of the min. battery
capacity.
4Max. recommended battery capacity (kWh or Ah) is the
largest battery bank size that the PV system can recharge from 50%
depth-of-discharge (DoD) on an average mid-summer day. In general,
other charging sources (such as an auxiliary generator or utility grid) will
be needed at other times of the year to bring the battery bank to a full state
of charge at regular intervals (at least once per week is recommended).
Without other charging sources, in order for this battery bank to remain fully
charged at times of the year other than the summer months, energy usage
must be equal to or less than that provided by the PV system on any given day.
This can be difficult to achieve, especially during winter months.
5Ave. recommended battery capacity (kWh or Ah) is the
largest battery bank size that the PV system can recharge from 50%
depth-of-discharge (DoD) on an average day. In general, other charging
sources (such as an auxiliary generator or utility grid) will be needed during
the winter months to bring the battery bank to a full state of charge at
regular intervals (at least once per week is recommended). Without other
charging sources, in order for this battery bank to remain fully charged in
winter months, energy usage must be equal to or less than that provided by
the PV system on any given day.
6 Battery bank voltage is the nominal value, not the
fully-charged voltage. 48V values are highlighted due to better economics and
efficiency of higher voltage battery charging systems utilizing 48V DC-to-AC
inverters.
7 Estimated cost of batteries includes batteries, cabling,
conduit and enclosure(s) - all of which are required for code compliant
systems.